400 Series Plug-in Smoke Detector
Models Available 1451 1451A 5451 Ionization Detector Ionization Detector, ULC Listed Thermal Rate-of-Rise
SSV120-6
Product Overview Low standby current Two visible LEDs "blink" in standby and provide a 360 field viewing angle Wide variety of mounting bases with built-in shorting spring Detector head plugs easily into base Built-in test switch Field sensitivity metering of detector to meet the requirements of NFPA 72 Built-in tamper-resistant feature SEMS screws for easy wiring Optional recessed mounting Removable cover and insect screen for field cleaning System Sensor's 400 Series plug-in smoke detectors are designed to meet the performance criteria designated by UL/ULC. The ion units have a sensing chamber sealed from back pressure air flow, dirt, and insects. This chamber is protected by a fine mesh screen which can be cleaned or replaced. Additional key features include a recessed mounting option, interchangeable ion, thermal detectors, a variety of mounting bases, and a full line of optional accessories. Ionization. All 400 Series ionization smoke detectors include a specially designed dual source, dual unipolar detector chamber design which will sense the presence of smoke particles produced by fast combustion as well as slow smoldering fires. This chamber exhibits increased stability, significantly reduces nuisance alarms, and provides better performance at higher air velocities. Thermal. The 400 Series thermal rate-of-rise with fixed heat detector contains a unique dual thermistor heat sensing circuit to provide maximum performance and solid state reliability. The Model 5451 is designed to initiate an alarm at 135F and to respond to a temperature increase in excess of 15 per minute. This enables the heat detector to communicate an alarm to the central control panel prior to reaching the static set point for these high rates of rise, providing a timely response to both rapid and slow temperature increases. This model should be used in applications where rapid response is desired and where rapid temperature increases would only be caused by a fire emergency.
Mounting Base Selection Guide Base Model Number B401B B401BR B402B B404B Version UL/ULC UL/ULC UL/ULC UL/ULC Loop Type 2-wire* 2-wire* 4-wire 4-wire Current Limit Resistor No Yes Yes Yes Alarm Contact Type -- -- Form A&C Form A&C+A Supervisory B406B B401 B401R UL/ULC/EN-54 UL/EN-54 EN-54 2-wire* 2-wire* 2-wire* No No Yes Form C -- -- 24VDC 12/24VDC 24VDC 12-100** 10-100** 10-62 Nominal Voltage 12/24VDC 24VDC 24VDC 120VAC Current Draw on Alarm (mA) 10-100** 10-62 14-39 75 mA AC Max
*Functionality contingent on panel compatibility. **Must be limited by control panel.
Relay Contact Ratings: Resistive or Inductive (60% power factor) load. Form A: 2.0A at 30 VAC/DC Form C: 0.6A at 110VDC, 2.0A at 30VDC 1.0A at 125VAC, 2.0A at 30VAC
Flangeless base Although B401B and B401 bases are capable of operating at 12 and 24 VDC, they cannot be used with the 5451 in 12 V applications.
Junction Box Selection Guide* Single Gang B401/B401R B401B/BR No Yes 3.5" Octagon No Yes Yes No 4" Octagon No Yes Yes Yes 4" Square No Yes Yes Yes 50 mm Yes No Yes No 60 mm Yes No Yes No 75 mm No No Yes No
B402B/B406B Yes B404B No
* Box depth contingent on base and wire size. Refer to National Electrical Code of local applicable codes for appropriate recommendations.
Specifications Operating Voltage/Alarm Current: Mounting base dependent (see char t on page 2) Standby Current: Ion: 120 A maximum Thermal: 100 A maximum Sensitivity: 1.9% + 6%/ft. Ion Weight: 1451: 0.5 lb. (227 gm) 5451: 0.3 lb. (136 gm) Size: 3.2"/8.1 cm height 4.0"/10.2 cm diameter, unflanged base 6.2"/15.7 cm diameter, flanged base Construction: Flame retardant Nor yl plastic Operating Temperature: 1451: 32F to 120F (0C to 49C) 5451: 32F to 100F (0C to 38C) Alarm Point, Thermal: 135F (57.2C) or 15F/min. rate of rise Humidity Range: 10 - 93% RH non-condensing Air Velocity Rating: Ionization: 1200 fpm maximum Smoke Detector Spacing: For ion detectors on smooth ceilings (as defined in NFPA 72), spacing of 30 feet (900 sq. ft.) may be used as a guide. For thermal detectors on smooth ceilings (as defined in NFPA 72), spacing of 50 feet (2500 sq. ft.) may be used. Other spacing may be used depending on ceiling height, high air movements, and other conditions or response requirements.
(-) (-)
OPTIONAL RA400Z
(-)
OPTIONAL
(-)
2
(-) 3
RA400Z
(-)
2
(-) 3
EOL RESISTOR
(+)
1
4
(+)
1
4
(+)
(+)
(+)
(+)
OPTIONAL FAULT TOLERANT WIRING
B401 Series
RED (+)
(+)
PURPLE
EOL POWER SUPERVISION RELAY, A77-716B
(-)
RA400Z (OPTIONAL) RA400Z (OPTIONAL)
(-)
5 1
10 89
(+) (-)
14 13 12 11
5 1
10 89
COM N.C. N.O.
(+)
AUXILIARY CONTACTS
14 13 12 11
COM N.C. N.O.
AUXILIARY CONTACTS
B402B
120 VAC
BL AC K BL AC K
ALARM CIRCUIT
120 VAC
BL BL AC AC
(-) 3
RA400Z (OPTIONAL)
2
4
(-) 3
RA400Z (OPTIONAL)
COM N.C. N.O.
2
4
(+)
6
7
14 5 13 12 11 10 89
1
1 (+)
AUXILIARY FORM C CONTACTS
5
6
7
10 89
14 13 12 11
COM N.C. N.O.
AUXILIARY FORM C CONTACTS
SUPERVISION CIRCUIT
EOL RESISTOR
ALARM CONTROL PANEL
ALARM CIRCUIT
B404B
(+)
PURPLE
2
2
BLK
EOL RESISTOR
2
3 5 1
4
2
3 5 1
4
14 13 12
COM N.C. N.O.
AUXILIARY CONTACTS
14 13 12
COM N.C. N.O.
AUXILIARY CONTACTS
(-)
B406B
OPTIONAL NFPA CLASS "A" WIRING
EOL RESISTOR
3
4
3
4
(-)
K
K
Ordering Information
Part No. 1451 1451A 5451 Description Ionization detector. Must be mounted to one of the B40X series bases listed in Mounting Base Guide. Same as above, Canadian model Fixed heat detector with rate-of-rise. Alarm point at 57.2C (135F). Must be mounted to one of the 400 Series Bases listed in Mounting Base Guide.
Accessories RA400Z B401BH MOD400R RMK400 SMK400 EOLR-1 RS14 DUST45 CRT400 M02-04-01 M02-09-00 XR5 XP-4
Description Remote annunciator for 2- or 4-wire systems, 3-32V. Use with ion and photo plug-in detectors. Fits standard U.S. single gang electrical box. Sounder base with B401. Requires an external 24 VDC power supply. Mounts to 4" square electrical box (11/2" minimum depth). Detector sensitivity test tool. (See below.) Use with most analog or digital multimeters. Satisfies requirement of NFPA 72 for sensitivity testing. (See below.) Recessed mounting kit for use with B401 or B401R mounting bases only. (See below.) Sur face mounting kit provides for entr y of sur face wiring conduit. For use with B401 or B401R mounting bases only. End of line relay for power super vision, 12/24 VDC, 4-wire only. Replacement insect screen for 1451. Replacement protective dust cover for plug-in 400 Series. Cover removal tool for 1451. Test magnet. Test magnet with 32 inch telescoping handle. Detector removal tool. Allows installation and/or removal of ion, photo, and thermal detector heads from base in high ceiling installations. Extension pole for XR5. Comes in three 5 ft. sections.
The MOD400R Field Sensitivity Test Module can be used with any standard DC voltmeter or multimeter to check the sensitivity range of System Sensor's detectors (satisfies NFPA 72 requirement for sensitivity testing).
System Sensor's Recessed Mounting Kit, RMK400, provides a simple installation solution where applications demand a lower profile smoke detector and reduces the depth of any 400 Series plug-in detector by almost an inch. A special metal mounting bracket secures the kit and the base to the junction box and ceiling panel. (For use with B401 and B401R bases only.)
System Sensor Sales and Service
System Sensor Headquarters 3825 Ohio Avenue St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor Europe Ph: 44.1403.891920 Fx: 44.1403.891921 System Sensor in China Ph: 86.29.8832.0119 Fx: 86.29.8832.5119 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor - Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor - Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor - India Ph: 91.124.237.1770 x.2700 Fx: 91.124.237.3118 System Sensor - Russia Ph: 70.95.937.7982 Fx: 70.95.937.7983
A05-0205-005*3/05*#1427
(c) 2005 System Sensor. The company reserves the right to change product specifications without notice.


▲Up To Search▲   

 
Price & Availability of 5451

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X